CRAC

CRAC Purification 18 Years of Dedication to Industrial Air Purification

首页 Clean room equipments

Clean laminar flow hood

Clean laminar flow hood

※ It is flexibly hoisted above the process points requiring high cleanliness to meet the requirements of local high cleanliness
※ The box can be made of wall panels, spray cold rolled steel or all stainless steel
※ Can be used alone, or multiple parallel to form a clean laminar flow belt.
※ Less investment, quick effect, easy installation, low operating costs.
※ Cleanliness: 100 grade (>0.5um dust ≤3.5 pieces/L
※ The average wind speed is 0.3-0.55m /s, and the wind speed at 1000mm below the outlet surface is not less than 0.25m/s
※ Noise <64dB(A).

Product Introduction

Applications

Mainly used in electronics, biology, medicine, food, precision instruments and other industries of dust-free aseptic operating environment, Provide local high cleanliness working environment.

Technical Parameters

Model number

Rated air volume (m³/h)

Overall dimension

(mm)

Work area size (mm)

Inlet size

(mm)

HEPA Filter specification

(mm)

Power source

Power dissipation

(KW)

CR 1220/610

1200

1360×740×850

1220×610

400×320

610×610×150,2个

Single-phase AC

220V/50HZ

(110V/60HZ)

1.0

CR 1220/915

1800

1360×1040×850

1220×915

400×320

915×610×150,2个

1.0

CR1220/1220

2400

1360×1360×850

1220×1220

400×320

1209×610×150,2个

1.3

CR 2500/915

4800

3200×1040×600

2500×915

1000×500

915×610×150,4个

Three-phase AC

380V/50HZ

(200V/60HZ)

1.8